Skip to Content

Dry cooler BC/BD-2x380CD5-B03 C

Dry cooler BC/BD-2x380CD5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x380CD5-B03 C

Heat rejection i
234.87 kW
Air flow
55,570 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 55,570 m³/h
External surface 1,523.5 m²
Inner volume 211.2 dm³
Fin materialAluminium
Net weight 1,220 kg
Fans
Quantity 6
Diameter 800 mm
Speed 435 rpm
Power 1,900 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 40.0 dB(A)
Sound power 72.0 dB(A)
Energy class B
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-2x380CD5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
234.871 kW Fluid flow 40.73 m³/h Pressure drop 61.0 kPa
Heat rejection · Low speed (Y)
178.428 kW Fluid flow 30.95 m³/h Pressure drop 37.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 143.80 not rated not rated not rated not rated not rated
40 234.87 143.62 not rated not rated not rated not rated
45 323.34 233.95 143.47 not rated not rated not rated
50 410.95 321.76 233.18 143.40 not rated not rated
55 498.17 408.74 320.42 232.62 143.48 not rated
60 585.18 495.35 406.87 319.43 232.38 143.76

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 110.39 not rated not rated not rated not rated not rated
40 178.43 110.17 not rated not rated not rated not rated
45 244.42 177.59 109.99 not rated not rated not rated
50 309.75 243.04 176.90 109.91 not rated not rated
55 374.77 307.85 241.90 176.42 109.93 not rated
60 439.63 372.37 306.29 241.08 176.21 110.14

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 234.871 40.73 61.0
Low speed (Y) 178.428 30.95 37.4

Dimensions

Dimension drawing of BC/BD-2x380CD5-B03 C
Dimension drawing
Dimensions as drawn
A 5600 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 5350 mm
H 1750 mm
I 2310 mm
K 5900 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5900 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.