BC/BD-2x380CD5-B03 C
234.87 kW
Defrost: None
Product code: BC/BD-2x380CC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 56,801 m³/h |
|---|---|
| External surface | 1,441.4 m² |
| Inner volume | 174.0 dm³ |
| Fin material | Aluminium |
| Net weight | 1,169 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | B |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2x380CC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 143.24 | not rated | not rated | not rated | not rated | not rated |
| 40 | 234.96 | 143.04 | not rated | not rated | not rated | not rated |
| 45 | 324.13 | 234.01 | 142.88 | not rated | not rated | not rated |
| 50 | 412.47 | 322.50 | 233.23 | 142.82 | not rated | not rated |
| 55 | 500.41 | 410.18 | 321.15 | 232.67 | 142.89 | not rated |
| 60 | 588.14 | 497.49 | 408.29 | 320.17 | 232.43 | 143.15 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 110.52 | not rated | not rated | not rated | not rated | not rated |
| 40 | 179.42 | 110.30 | not rated | not rated | not rated | not rated |
| 45 | 246.29 | 178.59 | 110.13 | not rated | not rated | not rated |
| 50 | 312.49 | 244.91 | 177.91 | 110.04 | not rated | not rated |
| 55 | 378.39 | 310.60 | 243.78 | 177.44 | 110.08 | not rated |
| 60 | 444.13 | 375.99 | 309.04 | 242.96 | 177.21 | 110.29 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 234.959 | 40.75 | 85.5 |
| Low speed (Y) | 179.421 | 31.12 | 53.0 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1750 mm |
| I | 2310 mm |
| K | 5900 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5900 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.