BC/BD-t-2x280JB5-B01 C
235.27 kW
Defrost: None
Product code: BC/BD-t-2X363AC5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 66,208 m³/h |
|---|---|
| External surface | 466.9 m² |
| Inner volume | 94.4 dm³ |
| Fin material | Aluminium |
| Net weight | 518 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 7,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-t-2X363AC5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 138.73 | not rated | not rated | not rated | not rated | not rated |
| 40 | 235.16 | 138.97 | not rated | not rated | not rated | not rated |
| 45 | 329.08 | 234.70 | 139.20 | not rated | not rated | not rated |
| 50 | 422.20 | 327.99 | 234.34 | 139.43 | not rated | not rated |
| 55 | 514.94 | 420.52 | 327.11 | 234.09 | 139.74 | not rated |
| 60 | 607.47 | 512.67 | 419.12 | 326.48 | 234.08 | 140.17 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 116.25 | not rated | not rated | not rated | not rated | not rated |
| 40 | 195.47 | 116.44 | not rated | not rated | not rated | not rated |
| 45 | 272.51 | 195.06 | 116.61 | not rated | not rated | not rated |
| 50 | 348.81 | 271.57 | 194.73 | 116.81 | not rated | not rated |
| 55 | 424.77 | 347.37 | 270.81 | 194.56 | 117.09 | not rated |
| 60 | 500.54 | 422.84 | 346.20 | 270.30 | 194.58 | 117.48 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 235.158 | 40.81 | 96.9 |
| Low speed (Y) | 195.467 | 33.90 | 69.8 |
| A | 3150 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 3500 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 3150 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.