Skip to Content

Dry cooler BC/BD-t-2x280JB5-B01 C

Dry cooler BC/BD-t-2x280JB5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2x280JB5-B01 C

Heat rejection i
235.27 kW
Air flow
78,859 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 78,859 m³/h
External surface 453.9 m²
Inner volume 75.9 dm³
Fin materialAluminium
Net weight 680 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-t-2x280JB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
235.267 kW Fluid flow 40.83 m³/h Pressure drop 38.9 kPa
Heat rejection · Low speed (Y)
186.577 kW Fluid flow 32.38 m³/h Pressure drop 25.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 133.33 not rated not rated not rated not rated not rated
40 235.27 134.30 not rated not rated not rated not rated
45 334.58 235.50 135.13 not rated not rated not rated
50 433.08 334.22 235.73 135.88 not rated not rated
55 531.17 432.16 333.96 236.02 136.61 not rated
60 629.07 529.74 431.44 333.88 236.45 137.39

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 106.65 not rated not rated not rated not rated not rated
40 186.58 107.41 not rated not rated not rated not rated
45 264.12 186.67 108.05 not rated not rated not rated
50 340.88 263.69 186.79 108.64 not rated not rated
55 417.30 339.98 263.38 186.97 109.23 not rated
60 493.49 415.93 339.26 263.24 187.27 109.85

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 235.267 40.83 38.9
Low speed (Y) 186.577 32.38 25.6

Dimensions

Dimension drawing of BC/BD-t-2x280JB5-B01 C
Dimension drawing
Dimensions as drawn
A 3850 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 3600 mm
H 1750 mm
I 2260 mm
K 4150 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4150 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.