Skip to Content

Dry cooler BC/BD-2x291BB5-B04 C

Dry cooler BC/BD-2x291BB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x291BB5-B04 C

Heat rejection i
234.81 kW
Air flow
104,626 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 104,626 m³/h
External surface 609.4 m²
Inner volume 117.0 dm³
Fin materialAluminium
Net weight 755 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 64.0 dB(A)
Sound power 96.4 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x291BB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
234.812 kW Fluid flow 40.76 m³/h Pressure drop 15.7 kPa
Heat rejection · Low speed (Y)
192.331 kW Fluid flow 33.38 m³/h Pressure drop 10.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 127.04 not rated not rated not rated not rated not rated
40 234.81 128.77 not rated not rated not rated not rated
45 340.17 235.83 130.24 not rated not rated not rated
50 444.83 340.65 236.73 131.55 not rated not rated
55 549.16 444.84 341.12 237.59 132.73 not rated
60 653.33 548.72 444.91 341.65 238.46 133.86

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 104.72 not rated not rated not rated not rated not rated
40 192.33 106.19 not rated not rated not rated not rated
45 277.57 193.16 107.46 not rated not rated not rated
50 362.10 277.94 193.90 108.57 not rated not rated
55 446.31 362.07 278.32 194.63 109.59 not rated
60 530.33 445.91 362.13 278.77 195.39 110.58

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 234.812 40.76 15.7
Low speed (Y) 192.331 33.38 10.9

Dimensions

Dimension drawing of BC/BD-2x291BB5-B04 C
Dimension drawing
Dimensions as drawn
A 3850 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 3600 mm
H 1750 mm
I 2310 mm
K 4150 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 4150 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.