Skip to Content

Dry cooler BC/BD-391GB1-B04 C

Dry cooler BC/BD-391GB1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-391GB1-B04 C

Heat rejection i
242.40 kW
Air flow
82,719 m³/h
Fans
3 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 82,719 m³/h
External surface 741.3 m²
Inner volume 90.1 dm³
Fin materialAluminium
Net weight 747 kg
Fans
Quantity 3
Diameter 910 mm
Speed 840 rpm
Power 8,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 63.0 dB(A)
Sound power 95.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-391GB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
242.396 kW Fluid flow 42.07 m³/h Pressure drop 98.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
196.524 kW Fluid flow 34.11 m³/h Pressure drop 67.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 140.36 not rated not rated not rated not rated not rated
40 242.40 140.74 not rated not rated not rated not rated
45 342.27 242.15 141.07 not rated not rated not rated
50 441.46 341.44 241.94 141.40 not rated not rated
55 540.30 440.06 340.74 241.82 141.74 not rated
60 638.97 538.36 438.87 340.23 241.86 142.15

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 114.74 not rated not rated not rated not rated not rated
40 196.52 115.02 not rated not rated not rated not rated
45 276.38 196.25 115.26 not rated not rated not rated
50 355.62 275.61 196.03 115.51 not rated not rated
55 434.56 354.37 274.98 195.91 115.78 not rated
60 513.33 432.84 353.32 274.51 195.92 116.13

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 242.396 42.07 98.2
Low speed (Y) 196.524 34.11 67.6

Dimensions

Dimension drawing of BC/BD-391GB1-B04 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 7300 mm
H 2400 mm
I 1190 mm
K 7850 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 7850 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.