Skip to Content

Dry cooler BC/BD-t-2X563AA5-B19 C

Dry cooler BC/BD-t-2X563AA5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X563AA5-B19 C

Heat rejection i
241.96 kW
Air flow
120,284 m³/h
Fans
10 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 120,284 m³/h
External surface 389.0 m²
Inner volume 85.6 dm³
Fin materialAluminium
Net weight 706 kg
Fans
Quantity 10
Diameter 630 mm
Speed 1,330 rpm
Power 12,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 62.0 dB(A)
Sound power 94.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-t-2X563AA5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
241.962 kW Fluid flow 41.99 m³/h Pressure drop 14.7 kPa
Heat rejection · Low speed (Y)
211.100 kW Fluid flow 36.63 m³/h Pressure drop 11.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 127.87 not rated not rated not rated not rated not rated
40 241.96 130.09 not rated not rated not rated not rated
45 353.29 243.24 131.93 not rated not rated not rated
50 463.85 353.95 244.35 133.53 not rated not rated
55 574.11 463.95 354.53 245.38 134.94 not rated
60 684.17 573.69 464.08 355.12 246.36 136.24

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 111.90 not rated not rated not rated not rated not rated
40 211.10 113.90 not rated not rated not rated not rated
45 307.51 212.23 115.57 not rated not rated not rated
50 403.16 308.06 213.19 117.01 not rated not rated
55 498.47 403.21 308.56 214.09 118.29 not rated
60 593.60 498.06 403.30 309.08 214.97 119.49

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 241.962 41.99 14.7
Low speed (Y) 211.100 36.63 11.5

Dimensions

Dimension drawing of BC/BD-t-2X563AA5-B19 C
Dimension drawing
Dimensions as drawn
A 4950 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 4600 mm
H 900 mm
I 2260 mm
K 5300 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 4950 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.