BC/BD-t-2X563AA5-B19 C
241.96 kW
Defrost: None
Product code: BC/BD-t-2x380JC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 55,957 m³/h |
|---|---|
| External surface | 907.8 m² |
| Inner volume | 127.2 dm³ |
| Fin material | Aluminium |
| Net weight | 1,026 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | B |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-2x380JC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 147.08 | not rated | not rated | not rated | not rated | not rated |
| 40 | 241.99 | 147.10 | not rated | not rated | not rated | not rated |
| 45 | 333.58 | 241.04 | 147.12 | not rated | not rated | not rated |
| 50 | 424.09 | 331.82 | 240.26 | 147.21 | not rated | not rated |
| 55 | 514.11 | 421.58 | 330.37 | 239.72 | 147.43 | not rated |
| 60 | 603.86 | 510.87 | 419.50 | 329.31 | 239.51 | 147.84 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 112.36 | not rated | not rated | not rated | not rated | not rated |
| 40 | 182.90 | 112.33 | not rated | not rated | not rated | not rated |
| 45 | 250.78 | 182.08 | 112.31 | not rated | not rated | not rated |
| 50 | 317.82 | 249.33 | 181.40 | 112.35 | not rated | not rated |
| 55 | 384.47 | 315.78 | 248.13 | 180.94 | 112.49 | not rated |
| 60 | 450.91 | 381.87 | 314.09 | 247.26 | 180.74 | 112.80 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 241.988 | 41.97 | 37.6 |
| Low speed (Y) | 182.904 | 31.72 | 22.7 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1750 mm |
| I | 2260 mm |
| K | 5900 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5900 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.