BC/BD-2X563CA1-B01 C
208.42 kW
Defrost: None
Product code: BC/BD-480AD5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 63,310 m³/h |
|---|---|
| External surface | 696.4 m² |
| Inner volume | 108.1 dm³ |
| Fin material | Aluminium |
| Net weight | 730 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-480AD5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 118.97 | not rated | not rated | not rated | not rated | not rated |
| 40 | 208.19 | 119.96 | not rated | not rated | not rated | not rated |
| 45 | 294.88 | 208.62 | 120.82 | not rated | not rated | not rated |
| 50 | 380.74 | 294.89 | 209.07 | 121.64 | not rated | not rated |
| 55 | 466.21 | 380.38 | 295.02 | 209.61 | 122.47 | not rated |
| 60 | 551.45 | 465.46 | 380.19 | 295.35 | 210.30 | 123.37 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 93.90 | not rated | not rated | not rated | not rated | not rated |
| 40 | 162.65 | 94.67 | not rated | not rated | not rated | not rated |
| 45 | 229.08 | 162.93 | 95.36 | not rated | not rated | not rated |
| 50 | 294.79 | 229.01 | 163.22 | 96.02 | not rated | not rated |
| 55 | 360.15 | 294.41 | 229.07 | 163.64 | 96.70 | not rated |
| 60 | 425.33 | 359.49 | 294.25 | 229.33 | 164.20 | 97.44 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 208.187 | 36.13 | 20.9 |
| Low speed (Y) | 162.646 | 28.23 | 13.5 |
| A | 5150 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4900 mm |
| H | 1200 mm |
| I | 1190 mm |
| K | 5450 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5450 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.