Skip to Content

Dry cooler BC/BD-491BC5-B04 C

Dry cooler BC/BD-491BC5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-491BC5-B04 C

Heat rejection i
290.86 kW
Air flow
99,712 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 99,712 m³/h
External surface 812.5 m²
Inner volume 122.3 dm³
Fin materialAluminium
Net weight 859 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 97.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-491BC5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
290.861 kW Fluid flow 50.48 m³/h Pressure drop 76.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
230.960 kW Fluid flow 40.08 m³/h Pressure drop 50.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 168.23 not rated not rated not rated not rated not rated
40 290.86 168.90 not rated not rated not rated not rated
45 410.88 290.92 169.50 not rated not rated not rated
50 530.06 410.39 291.01 170.09 not rated not rated
55 648.84 529.04 410.01 291.19 170.70 not rated
60 767.40 647.30 528.21 409.84 291.56 171.39

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 134.82 not rated not rated not rated not rated not rated
40 230.96 135.34 not rated not rated not rated not rated
45 324.79 230.95 135.82 not rated not rated not rated
50 417.86 324.33 231.01 136.31 not rated not rated
55 510.58 416.97 324.02 231.20 136.84 not rated
60 603.11 509.27 416.31 323.95 231.56 137.46

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 290.861 50.48 76.2
Low speed (Y) 230.960 40.08 50.6

Dimensions

Dimension drawing of BC/BD-491BC5-B04 C
Dimension drawing
Dimensions as drawn
A 7350 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 7100 mm
H 1750 mm
I 1190 mm
K 7650 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7650 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.