Dry cooler BC/BD-680AC1-B01I C

Dry cooler BC/BD-680AC1-B01I C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-680AC1-B01I C

Heat rejection i
290.63 kW
Air flow
93,297 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 93,297 m³/h
External surface 988.4 m²
Inner volume 125.2 dm³
Fin materialAluminium
Net weight 1,028 kg
Fans
Quantity 6
Diameter 800 mm
Speed 880 rpm
Power 11,700 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.5 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-680AC1-B01I C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · Single phase
290.634 kW Fluid flow 50.44 m³/h Pressure drop 15.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Single phase

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 160.87 not rated not rated not rated not rated not rated
40 290.63 162.87 not rated not rated not rated not rated
45 416.37 291.60 164.59 not rated not rated not rated
50 540.81 416.58 292.51 166.15 not rated not rated
55 664.63 540.34 416.88 293.48 167.63 not rated
60 788.13 663.55 540.11 417.41 294.56 169.11

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 290.634 50.44 15.2

Dimensions

Dimension drawing of BC/BD-680AC1-B01I C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 7300 mm
H 1200 mm
I 1190 mm
K 7850 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7550 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.