Dry cooler BC/BD-t-2X380GC5-B01 C

Dry cooler BC/BD-t-2X380GC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X380GC5-B01 C

Heat rejection i
290.55 kW
Air flow
89,345 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 89,345 m³/h
External surface 544.7 m²
Inner volume 103.2 dm³
Fin materialAluminium
Net weight 822 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 90.9 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-t-2X380GC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
290.553 kW Fluid flow 50.43 m³/h Pressure drop 27.7 kPa
Heat rejection · Low speed (Y)
225.887 kW Fluid flow 39.20 m³/h Pressure drop 17.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 164.44 not rated not rated not rated not rated not rated
40 290.55 166.09 not rated not rated not rated not rated
45 412.92 291.43 167.57 not rated not rated not rated
50 534.09 413.25 292.33 168.97 not rated not rated
55 654.68 533.90 413.71 293.34 170.34 not rated
60 774.92 653.99 534.01 414.46 294.54 171.78

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 129.15 not rated not rated not rated not rated not rated
40 225.89 130.48 not rated not rated not rated not rated
45 319.16 226.53 131.68 not rated not rated not rated
50 411.36 319.34 227.21 132.80 not rated not rated
55 503.05 411.14 319.67 227.96 133.93 not rated
60 594.45 502.46 411.19 320.26 228.95 135.24

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 290.553 50.43 27.7
Low speed (Y) 225.887 39.20 17.6

Dimensions

Dimension drawing of BC/BD-t-2X380GC5-B01 C
Dimension drawing
Dimensions as drawn
A 3500 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 3250 mm
H 1050 mm
I 2260 mm
K 3800 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 3500 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.