Product code: BC/BD-2X480HB5-B01 C

Heat rejection i
290.28 kW
Air flow
137,909 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 137,909 m³/h
External surface 544.7 m²
Inner volume 103.2 dm³
Fin materialAluminium
Net weight 1,015 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 90.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2X480HB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
290.278 kW Fluid flow 50.38 m³/h Pressure drop 65.3 kPa
Heat rejection · Low speed (Y)
235.732 kW Fluid flow 40.92 m³/h Pressure drop 45.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 163.67 not rated not rated not rated not rated not rated
40 290.28 164.96 not rated not rated not rated not rated
45 414.61 291.17 166.11 not rated not rated not rated
50 538.25 415.19 292.04 167.18 not rated not rated
55 661.55 538.55 415.83 292.93 168.23 not rated
60 784.68 661.59 538.98 416.59 293.90 169.28

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 133.65 not rated not rated not rated not rated not rated
40 235.73 134.68 not rated not rated not rated not rated
45 335.71 236.36 135.59 not rated not rated not rated
50 435.04 336.04 236.98 136.44 not rated not rated
55 534.10 435.10 336.43 237.63 137.27 not rated
60 632.97 533.89 435.28 336.94 238.38 138.13

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 290.278 50.38 65.3
Low speed (Y) 235.732 40.92 45.2

Dimensions

Dimension drawing of BC/BD-2X480HB5-B01 C
Dimension drawing
Dimensions as drawn
A 4550 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 4300 mm
H 1050 mm
I 2260 mm
K 4850 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 4550 mm
Width 2310 mm
Height 1450 mm

Downloads