BC/BD-t-2X380GC5-B01 C
290.55 kW
Defrost: None
Product code: BC/BD-2X563CD5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 79,693 m³/h |
|---|---|
| External surface | 1,305.8 m² |
| Inner volume | 202.1 dm³ |
| Fin material | Aluminium |
| Net weight | 1,032 kg |
| Quantity | 10 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 6,000 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 84.4 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X563CD5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 167.02 | not rated | not rated | not rated | not rated | not rated |
| 40 | 290.45 | 168.32 | not rated | not rated | not rated | not rated |
| 45 | 409.43 | 290.52 | 169.41 | not rated | not rated | not rated |
| 50 | 527.03 | 408.69 | 290.70 | 170.43 | not rated | not rated |
| 55 | 643.97 | 525.51 | 408.16 | 291.02 | 171.45 | not rated |
| 60 | 760.54 | 641.74 | 524.37 | 407.97 | 291.59 | 172.56 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 290.446 | 50.41 | 14.4 |
| A | 4800 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4600 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 5100 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5100 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.