Skip to Content

Dry cooler BC/BD-491HB5-B04 C

Dry cooler BC/BD-491HB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-491HB5-B04 C

Heat rejection i
311.83 kW
Air flow
108,947 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 108,947 m³/h
External surface 794.9 m²
Inner volume 183.1 dm³
Fin materialAluminium
Net weight 979 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 63.0 dB(A)
Sound power 96.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-491HB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
311.828 kW Fluid flow 54.12 m³/h Pressure drop 68.1 kPa
Heat rejection · Low speed (Y)
251.074 kW Fluid flow 43.58 m³/h Pressure drop 46.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 180.86 not rated not rated not rated not rated not rated
40 311.83 181.31 not rated not rated not rated not rated
45 440.13 311.55 181.72 not rated not rated not rated
50 567.56 439.17 311.33 182.13 not rated not rated
55 694.60 565.94 438.35 311.22 182.57 not rated
60 821.40 692.31 564.55 437.77 311.30 183.10

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 146.72 not rated not rated not rated not rated not rated
40 251.07 147.10 not rated not rated not rated not rated
45 353.07 250.84 147.44 not rated not rated not rated
50 454.29 352.27 250.67 147.79 not rated not rated
55 555.15 452.96 351.64 250.62 148.20 not rated
60 655.81 553.30 451.88 351.24 250.76 148.67

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 311.828 54.12 68.1
Low speed (Y) 251.074 43.58 46.4

Dimensions

Dimension drawing of BC/BD-491HB5-B04 C
Dimension drawing
Dimensions as drawn
A 9950 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 9700 mm
H 2400 mm
I 1190 mm
K 10250 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10250 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.