Skip to Content

Dry cooler BC/BD-t-2x580GC1-B03 C

Dry cooler BC/BD-t-2x580GC1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2x580GC1-B03 C

Heat rejection i
312.03 kW
Air flow
70,841 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 70,841 m³/h
External surface 1,071.6 m²
Inner volume 144.3 dm³
Fin materialAluminium
Net weight 1,308 kg
Fans
Quantity 10
Diameter 800 mm
Speed 435 rpm
Power 3,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 42.0 dB(A)
Sound power 74.0 dB(A)
Energy class C
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-t-2x580GC1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
312.027 kW Fluid flow 54.12 m³/h Pressure drop 47.7 kPa
Heat rejection · Low speed (Y)
not rated

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 190.46 not rated not rated not rated not rated not rated
40 312.03 190.94 not rated not rated not rated not rated
45 429.32 311.65 191.46 not rated not rated not rated
50 545.21 428.27 311.53 192.11 not rated not rated
55 660.45 543.55 427.66 311.77 192.96 not rated
60 775.33 658.22 542.50 427.62 312.48 194.10

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 not rated not rated not rated not rated not rated not rated
40 not rated not rated not rated not rated not rated not rated
45 not rated not rated not rated not rated not rated not rated
50 not rated not rated not rated 141.19 not rated not rated
55 not rated not rated not rated 226.12 141.73 not rated
60 not rated not rated not rated 308.22 226.51 142.92

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 312.027 54.12 47.7
Low speed (Y) — — —

Dimensions

Dimension drawing of BC/BD-t-2x580GC1-B03 C
Dimension drawing
Dimensions as drawn
A 5600 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 5350 mm
H 1050 mm
I 2260 mm
K 5900 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5900 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.