Skip to Content

Dry cooler BC/BD-t-680GC1-B01 C

Dry cooler BC/BD-t-680GC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-680GC1-B01 C

Heat rejection i
311.99 kW
Air flow
86,846 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 86,846 m³/h
External surface 651.4 m²
Inner volume 84.4 dm³
Fin materialAluminium
Net weight 897 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.3 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-t-680GC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
311.985 kW Fluid flow 54.15 m³/h Pressure drop 29.7 kPa
Heat rejection · Low speed (Y)
238.462 kW Fluid flow 41.36 m³/h Pressure drop 18.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 178.32 not rated not rated not rated not rated not rated
40 311.99 179.97 not rated not rated not rated not rated
45 441.17 312.71 181.47 not rated not rated not rated
50 568.89 441.19 313.44 182.89 not rated not rated
55 695.92 568.30 441.45 314.39 184.33 not rated
60 822.55 694.75 568.11 442.07 315.60 185.88

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 137.98 not rated not rated not rated not rated not rated
40 238.46 139.27 not rated not rated not rated not rated
45 335.01 238.95 140.44 not rated not rated not rated
50 430.25 334.95 239.52 141.56 not rated not rated
55 524.87 429.72 335.12 240.24 142.72 not rated
60 619.14 523.90 429.54 335.60 241.23 143.95

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 311.985 54.15 29.7
Low speed (Y) 238.462 41.36 18.3

Dimensions

Dimension drawing of BC/BD-t-680GC1-B01 C
Dimension drawing
Dimensions as drawn
A 6650 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 6400 mm
H 1050 mm
I 1180 mm
K 6950 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6650 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.