BC/BD-t-550AA5-B09 C
80.63 kW
Defrost: None
Product code: BC/BD-t-2x180JC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 18,652 m³/h |
|---|---|
| External surface | 302.6 m² |
| Inner volume | 44.7 dm³ |
| Fin material | Aluminium |
| Net weight | 390 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 35.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | B |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-t-2x180JC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 49.10 | not rated | not rated | not rated | not rated | not rated |
| 40 | 80.73 | 49.11 | not rated | not rated | not rated | not rated |
| 45 | 111.25 | 80.41 | 49.11 | not rated | not rated | not rated |
| 50 | 141.42 | 110.66 | 80.14 | 49.13 | not rated | not rated |
| 55 | 171.43 | 140.58 | 110.18 | 79.96 | 49.20 | not rated |
| 60 | 201.34 | 170.34 | 139.89 | 109.82 | 79.89 | 49.34 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 37.51 | not rated | not rated | not rated | not rated | not rated |
| 40 | 61.01 | 37.50 | not rated | not rated | not rated | not rated |
| 45 | 83.63 | 60.73 | 37.49 | not rated | not rated | not rated |
| 50 | 105.97 | 83.14 | 60.51 | 37.49 | not rated | not rated |
| 55 | 128.19 | 105.29 | 82.74 | 60.35 | 37.54 | not rated |
| 60 | 150.34 | 127.32 | 104.73 | 82.45 | 60.28 | 37.64 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 80.728 | 14.00 | 37.8 |
| Low speed (Y) | 61.011 | 10.58 | 22.9 |
| A | 2100 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1850 mm |
| H | 1750 mm |
| I | 2260 mm |
| K | 2400 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2400 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.