BE-t-191HB5-B04 C
104.24 kW
Defrost: None
Product code: BE-191DC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 29,090 m³/h |
|---|---|
| External surface | 423.0 m² |
| Inner volume | 50.2 dm³ |
| Fin material | Aluminium |
| Net weight | 410 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-191DC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 62.75 | not rated | not rated | not rated | not rated | not rated |
| 40 | 105.90 | 62.77 | not rated | not rated | not rated | not rated |
| 45 | 147.84 | 105.53 | 62.78 | not rated | not rated | not rated |
| 50 | 189.42 | 147.12 | 105.18 | 62.81 | not rated | not rated |
| 55 | 230.81 | 188.36 | 146.49 | 104.92 | 62.85 | not rated |
| 60 | 272.10 | 229.42 | 187.43 | 145.97 | 104.75 | 62.96 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 49.94 | not rated | not rated | not rated | not rated | not rated |
| 40 | 83.65 | 49.95 | not rated | not rated | not rated | not rated |
| 45 | 116.34 | 83.31 | 49.94 | not rated | not rated | not rated |
| 50 | 148.70 | 115.71 | 83.01 | 49.95 | not rated | not rated |
| 55 | 180.90 | 147.78 | 115.15 | 82.77 | 49.96 | not rated |
| 60 | 213.02 | 179.71 | 146.98 | 114.70 | 82.62 | 50.04 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 105.896 | 18.38 | 54.0 |
| Low speed (Y) | 83.651 | 14.51 | 35.5 |
| A | 1958 mm |
|---|---|
| B | 1210 mm |
| C | 2260 mm |
| F | 1050 mm |
| G | 2860 mm |
| E1 | 1830 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2860 mm |
|---|---|
| Width | 1210 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.