Skip to Content

Dry cooler BE-280CD1-B01 C

Dry cooler BE-280CD1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-280CD1-B01 C

Heat rejection i
204.85 kW
Air flow
44,545 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 44,545 m³/h
External surface 1,881.1 m²
Inner volume 204.5 dm³
Fin materialAluminium
Net weight 1,076 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-280CD1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
204.853 kW Fluid flow 35.53 m³/h Pressure drop 103.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
155.035 kW Fluid flow 26.89 m³/h Pressure drop 63.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 128.75 not rated not rated not rated not rated not rated
40 204.85 127.91 not rated not rated not rated not rated
45 278.84 203.09 127.15 not rated not rated not rated
50 352.16 276.23 201.54 126.53 not rated not rated
55 425.18 348.73 273.95 200.25 126.08 not rated
60 498.04 420.95 345.74 272.05 199.29 125.84

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 98.37 not rated not rated not rated not rated not rated
40 155.04 97.66 not rated not rated not rated not rated
45 210.13 153.62 97.04 not rated not rated not rated
50 264.75 208.07 152.37 96.52 not rated not rated
55 319.15 262.06 206.26 151.34 96.14 not rated
60 373.45 315.84 259.70 204.76 150.57 95.95

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 204.853 35.53 103.9
Low speed (Y) 155.035 26.89 63.3

Dimensions

Dimension drawing of BE-280CD1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 5260 mm
F 1050 mm
G 5860 mm
E1 2430 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 5860 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.