BE-2x280BB5-B01C C
206.37 kW
Defrost: None
Product code: BE-2x191DC1-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 57,619 m³/h |
|---|---|
| External surface | 774.7 m² |
| Inner volume | 97.3 dm³ |
| Fin material | Aluminium |
| Net weight | 991 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-2x191DC1-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 121.77 | not rated | not rated | not rated | not rated | not rated |
| 40 | 205.95 | 121.86 | not rated | not rated | not rated | not rated |
| 45 | 287.84 | 205.29 | 121.91 | not rated | not rated | not rated |
| 50 | 369.02 | 286.53 | 204.71 | 121.98 | not rated | not rated |
| 55 | 449.87 | 367.08 | 285.38 | 204.23 | 122.11 | not rated |
| 60 | 530.52 | 447.31 | 365.39 | 284.46 | 203.96 | 122.32 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 97.07 | not rated | not rated | not rated | not rated | not rated |
| 40 | 162.91 | 97.10 | not rated | not rated | not rated | not rated |
| 45 | 226.81 | 162.29 | 97.12 | not rated | not rated | not rated |
| 50 | 290.08 | 225.65 | 161.76 | 97.15 | not rated | not rated |
| 55 | 353.06 | 288.39 | 224.64 | 161.34 | 97.23 | not rated |
| 60 | 415.88 | 350.86 | 286.93 | 223.83 | 161.09 | 97.37 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 205.950 | 35.74 | 66.2 |
| Low speed (Y) | 162.907 | 28.26 | 43.5 |
| A | 2910 mm |
|---|---|
| B | 2400 mm |
| C | 2250 mm |
| F | 2330 mm |
| G | 2850 mm |
| E1 | 1850 mm |
| H | 2500 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2910 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.