Dry cooler BE-291CB5-B04 C

Dry cooler BE-291CB5-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-291CB5-B04 C

Heat rejection i
205.15 kW
Air flow
60,317 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • D
    Number of fans per row: 2 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 60,317 m³/h
External surface 955.1 m²
Inner volume 131.5 dm³
Fin materialAluminium
Net weight 862 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-291CB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
205.146 kW Fluid flow 35.61 m³/h Pressure drop 82.1 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
164.898 kW Fluid flow 28.62 m³/h Pressure drop 55.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 121.78 not rated not rated not rated not rated not rated
40 205.15 121.66 not rated not rated not rated not rated
45 286.56 204.34 121.53 not rated not rated not rated
50 367.35 285.14 203.62 121.45 not rated not rated
55 447.83 365.28 283.86 203.04 121.41 not rated
60 528.15 445.17 363.47 282.78 202.62 121.47

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 98.64 not rated not rated not rated not rated not rated
40 164.90 98.48 not rated not rated not rated not rated
45 229.46 164.12 98.34 not rated not rated not rated
50 293.50 228.16 163.46 98.21 not rated not rated
55 357.28 291.67 227.01 162.90 98.16 not rated
60 420.93 354.93 290.05 226.05 162.50 98.19

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 205.146 35.61 82.1
Low speed (Y) 164.898 28.62 55.7

Dimensions

Dimension drawing of BE-291CB5-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1210 mm
C 5260 mm
F 1050 mm
G 5860 mm
E1 2430 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 5860 mm
Width 1210 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.