BE-380BC5-B01 C
205.40 kW
Defrost: None
Product code: BE-291CB5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 60,317 m³/h |
|---|---|
| External surface | 955.1 m² |
| Inner volume | 131.5 dm³ |
| Fin material | Aluminium |
| Net weight | 862 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-291CB5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 121.78 | not rated | not rated | not rated | not rated | not rated |
| 40 | 205.15 | 121.66 | not rated | not rated | not rated | not rated |
| 45 | 286.56 | 204.34 | 121.53 | not rated | not rated | not rated |
| 50 | 367.35 | 285.14 | 203.62 | 121.45 | not rated | not rated |
| 55 | 447.83 | 365.28 | 283.86 | 203.04 | 121.41 | not rated |
| 60 | 528.15 | 445.17 | 363.47 | 282.78 | 202.62 | 121.47 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 98.64 | not rated | not rated | not rated | not rated | not rated |
| 40 | 164.90 | 98.48 | not rated | not rated | not rated | not rated |
| 45 | 229.46 | 164.12 | 98.34 | not rated | not rated | not rated |
| 50 | 293.50 | 228.16 | 163.46 | 98.21 | not rated | not rated |
| 55 | 357.28 | 291.67 | 227.01 | 162.90 | 98.16 | not rated |
| 60 | 420.93 | 354.93 | 290.05 | 226.05 | 162.50 | 98.19 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 205.146 | 35.61 | 82.1 |
| Low speed (Y) | 164.898 | 28.62 | 55.7 |
| A | 1958 mm |
|---|---|
| B | 1210 mm |
| C | 5260 mm |
| F | 1050 mm |
| G | 5860 mm |
| E1 | 2430 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 5860 mm |
|---|---|
| Width | 1210 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.