BE-2x191CC5-C04C C
211.69 kW
Defrost: None
Product code: BE-291DC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 58,181 m³/h |
|---|---|
| External surface | 846.1 m² |
| Inner volume | 96.8 dm³ |
| Fin material | Aluminium |
| Net weight | 753 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-291DC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 125.34 | not rated | not rated | not rated | not rated | not rated |
| 40 | 211.66 | 125.41 | not rated | not rated | not rated | not rated |
| 45 | 295.56 | 210.93 | 125.44 | not rated | not rated | not rated |
| 50 | 378.72 | 294.13 | 210.24 | 125.50 | not rated | not rated |
| 55 | 461.50 | 376.60 | 292.86 | 209.74 | 125.60 | not rated |
| 60 | 544.09 | 458.73 | 374.75 | 291.84 | 209.40 | 125.80 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 99.78 | not rated | not rated | not rated | not rated | not rated |
| 40 | 167.21 | 99.80 | not rated | not rated | not rated | not rated |
| 45 | 232.60 | 166.54 | 99.79 | not rated | not rated | not rated |
| 50 | 297.31 | 231.33 | 165.94 | 99.80 | not rated | not rated |
| 55 | 361.72 | 295.48 | 230.22 | 165.47 | 99.84 | not rated |
| 60 | 425.96 | 359.35 | 293.89 | 229.33 | 165.16 | 100.00 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 211.663 | 36.73 | 53.7 |
| Low speed (Y) | 167.207 | 29.00 | 35.1 |
| A | 1958 mm |
|---|---|
| B | 1210 mm |
| C | 4060 mm |
| F | 1050 mm |
| G | 4660 mm |
| E1 | 1830 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 4660 mm |
|---|---|
| Width | 1210 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.