Skip to Content

Dry cooler BE-380AB1-B01 C

Dry cooler BE-380AB1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-380AB1-B01 C

Heat rejection i
213.71 kW
Air flow
64,656 m³/h
Fans
3 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 64,656 m³/h
External surface 847.2 m²
Inner volume 102.4 dm³
Fin materialAluminium
Net weight 856 kg
Fans
Quantity 3
Diameter 800 mm
Speed 900 rpm
Power 5,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 53.0 dB(A)
Sound power 85.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-380AB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
213.706 kW Fluid flow 37.09 m³/h Pressure drop 70.0 kPa
Heat rejection · Low speed (Y)
169.889 kW Fluid flow 29.48 m³/h Pressure drop 46.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 125.08 not rated not rated not rated not rated not rated
40 213.71 125.25 not rated not rated not rated not rated
45 300.22 213.18 125.39 not rated not rated not rated
50 386.02 299.06 212.73 125.53 not rated not rated
55 471.49 384.25 298.06 212.38 125.70 not rated
60 556.78 469.14 382.72 297.25 212.19 125.96

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 100.32 not rated not rated not rated not rated not rated
40 169.89 100.41 not rated not rated not rated not rated
45 237.59 169.37 100.47 not rated not rated not rated
50 304.69 236.53 168.90 100.54 not rated not rated
55 371.51 303.12 235.61 168.55 100.67 not rated
60 438.17 369.43 301.75 234.88 168.35 100.86

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 213.706 37.09 70.0
Low speed (Y) 169.889 29.48 46.4

Dimensions

Dimension drawing of BE-380AB1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 4060 mm
F 1050 mm
G 4660 mm
E1 1230 mm
E2 1200 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 4660 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.