Skip to Content

Dry cooler BE-2x191CC5-C04C C

Dry cooler BE-2x191CC5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x191CC5-C04C C

Heat rejection i
211.69 kW
Air flow
58,302 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 58,302 m³/h
External surface 934.4 m²
Inner volume 132.0 dm³
Fin materialAluminium
Net weight 1,048 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-2x191CC5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
211.689 kW Fluid flow 36.74 m³/h Pressure drop 98.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
168.438 kW Fluid flow 29.21 m³/h Pressure drop 65.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 126.49 not rated not rated not rated not rated not rated
40 211.69 126.34 not rated not rated not rated not rated
45 294.77 210.82 126.19 not rated not rated not rated
50 377.19 293.25 210.04 126.09 not rated not rated
55 459.28 375.01 291.91 209.42 126.06 not rated
60 541.19 456.47 373.12 290.82 209.01 126.16

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 101.55 not rated not rated not rated not rated not rated
40 168.44 101.36 not rated not rated not rated not rated
45 233.58 167.65 101.19 not rated not rated not rated
50 298.13 232.22 166.94 101.06 not rated not rated
55 362.40 296.22 231.03 166.38 100.99 not rated
60 426.53 359.96 294.56 230.06 166.00 101.05

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 211.689 36.74 98.9
Low speed (Y) 168.438 29.21 65.8

Dimensions

Dimension drawing of BE-2x191CC5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 2850 mm
F 2230 mm
G 3450 mm
E1 2450 mm
H 3100 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 2850 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.