BE-291DC1-B04 C
211.66 kW
Defrost: None
Product code: BE-2x191CC5-C04C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 58,302 m³/h |
|---|---|
| External surface | 934.4 m² |
| Inner volume | 132.0 dm³ |
| Fin material | Aluminium |
| Net weight | 1,048 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-2x191CC5-C04C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 126.49 | not rated | not rated | not rated | not rated | not rated |
| 40 | 211.69 | 126.34 | not rated | not rated | not rated | not rated |
| 45 | 294.77 | 210.82 | 126.19 | not rated | not rated | not rated |
| 50 | 377.19 | 293.25 | 210.04 | 126.09 | not rated | not rated |
| 55 | 459.28 | 375.01 | 291.91 | 209.42 | 126.06 | not rated |
| 60 | 541.19 | 456.47 | 373.12 | 290.82 | 209.01 | 126.16 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 101.55 | not rated | not rated | not rated | not rated | not rated |
| 40 | 168.44 | 101.36 | not rated | not rated | not rated | not rated |
| 45 | 233.58 | 167.65 | 101.19 | not rated | not rated | not rated |
| 50 | 298.13 | 232.22 | 166.94 | 101.06 | not rated | not rated |
| 55 | 362.40 | 296.22 | 231.03 | 166.38 | 100.99 | not rated |
| 60 | 426.53 | 359.96 | 294.56 | 230.06 | 166.00 | 101.05 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 211.689 | 36.74 | 98.9 |
| Low speed (Y) | 168.438 | 29.21 | 65.8 |
| A | 2511 mm |
|---|---|
| B | 2300 mm |
| C | 2850 mm |
| F | 2230 mm |
| G | 3450 mm |
| E1 | 2450 mm |
| H | 3100 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2850 mm |
|---|---|
| Width | 2300 mm |
| Height | 2511 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.