Skip to Content

Dry cooler BE-2x191CB1-B04T C

Dry cooler BE-2x191CB1-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x191CB1-B04T C

Heat rejection i
214.19 kW
Air flow
59,738 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 59,738 m³/h
External surface 1,005.5 m²
Inner volume 125.9 dm³
Fin materialAluminium
Net weight 1,108 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-2x191CB1-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
214.192 kW Fluid flow 37.17 m³/h Pressure drop 117.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
171.115 kW Fluid flow 29.68 m³/h Pressure drop 78.6 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 127.78 not rated not rated not rated not rated not rated
40 214.19 127.60 not rated not rated not rated not rated
45 298.49 213.28 127.43 not rated not rated not rated
50 382.13 296.90 212.47 127.30 not rated not rated
55 465.45 379.87 295.49 211.79 127.25 not rated
60 548.58 462.53 377.87 294.32 211.32 127.31

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 102.96 not rated not rated not rated not rated not rated
40 171.12 102.75 not rated not rated not rated not rated
45 237.51 170.26 102.54 not rated not rated not rated
50 303.32 236.08 169.51 102.39 not rated not rated
55 368.86 301.31 234.80 168.89 102.27 not rated
60 434.24 366.28 299.53 233.75 168.44 102.30

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 214.192 37.17 117.2
Low speed (Y) 171.115 29.68 78.6

Dimensions

Dimension drawing of BE-2x191CB1-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 2850 mm
F 2330 mm
G 3450 mm
E1 2450 mm
H 3100 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 3450 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.