BE-t-2x191HC5-C04C C
214.16 kW
Defrost: None
Product code: BE-2x191CB1-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 59,738 m³/h |
|---|---|
| External surface | 1,005.5 m² |
| Inner volume | 125.9 dm³ |
| Fin material | Aluminium |
| Net weight | 1,108 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-2x191CB1-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 127.78 | not rated | not rated | not rated | not rated | not rated |
| 40 | 214.19 | 127.60 | not rated | not rated | not rated | not rated |
| 45 | 298.49 | 213.28 | 127.43 | not rated | not rated | not rated |
| 50 | 382.13 | 296.90 | 212.47 | 127.30 | not rated | not rated |
| 55 | 465.45 | 379.87 | 295.49 | 211.79 | 127.25 | not rated |
| 60 | 548.58 | 462.53 | 377.87 | 294.32 | 211.32 | 127.31 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 102.96 | not rated | not rated | not rated | not rated | not rated |
| 40 | 171.12 | 102.75 | not rated | not rated | not rated | not rated |
| 45 | 237.51 | 170.26 | 102.54 | not rated | not rated | not rated |
| 50 | 303.32 | 236.08 | 169.51 | 102.39 | not rated | not rated |
| 55 | 368.86 | 301.31 | 234.80 | 168.89 | 102.27 | not rated |
| 60 | 434.24 | 366.28 | 299.53 | 233.75 | 168.44 | 102.30 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 214.192 | 37.17 | 117.2 |
| Low speed (Y) | 171.115 | 29.68 | 78.6 |
| A | 2880 mm |
|---|---|
| B | 2400 mm |
| C | 2850 mm |
| F | 2330 mm |
| G | 3450 mm |
| E1 | 2450 mm |
| H | 3100 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3450 mm |
|---|---|
| Width | 2400 mm |
| Height | 2880 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.