BE-t-2x180HC1-B01T C
196.45 kW
Defrost: None
Product code: BE-291DC5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 58,551 m³/h |
|---|---|
| External surface | 716.8 m² |
| Inner volume | 96.8 dm³ |
| Fin material | Aluminium |
| Net weight | 735 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-291DC5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 115.49 | not rated | not rated | not rated | not rated | not rated |
| 40 | 196.61 | 115.65 | not rated | not rated | not rated | not rated |
| 45 | 275.61 | 196.07 | 115.76 | not rated | not rated | not rated |
| 50 | 353.93 | 274.48 | 195.59 | 115.87 | not rated | not rated |
| 55 | 431.95 | 352.22 | 273.47 | 195.22 | 116.02 | not rated |
| 60 | 509.76 | 429.65 | 350.70 | 272.67 | 194.99 | 116.24 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 92.72 | not rated | not rated | not rated | not rated | not rated |
| 40 | 156.80 | 92.82 | not rated | not rated | not rated | not rated |
| 45 | 219.01 | 156.29 | 92.88 | not rated | not rated | not rated |
| 50 | 280.65 | 217.98 | 155.82 | 92.95 | not rated | not rated |
| 55 | 342.01 | 279.13 | 217.09 | 155.46 | 93.05 | not rated |
| 60 | 403.23 | 340.02 | 277.81 | 216.36 | 155.24 | 93.23 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 196.614 | 34.13 | 47.1 |
| Low speed (Y) | 156.799 | 27.21 | 31.4 |
| A | 1958 mm |
|---|---|
| B | 1210 mm |
| C | 4060 mm |
| F | 1050 mm |
| G | 4660 mm |
| E1 | 1830 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 4660 mm |
|---|---|
| Width | 1210 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.