BE-291DC5-B04 C
196.61 kW
Defrost: None
Product code: BE-t-2x180HC1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 43,306 m³/h |
|---|---|
| External surface | 774.7 m² |
| Inner volume | 97.3 dm³ |
| Fin material | Aluminium |
| Net weight | 981 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-t-2x180HC1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 121.12 | not rated | not rated | not rated | not rated | not rated |
| 40 | 196.45 | 120.71 | not rated | not rated | not rated | not rated |
| 45 | 269.08 | 195.06 | 120.33 | not rated | not rated | not rated |
| 50 | 340.84 | 266.84 | 193.83 | 120.03 | not rated | not rated |
| 55 | 412.20 | 337.80 | 264.88 | 192.83 | 119.85 | not rated |
| 60 | 483.35 | 408.38 | 335.14 | 263.27 | 192.11 | 119.84 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 92.48 | not rated | not rated | not rated | not rated | not rated |
| 40 | 148.38 | 92.12 | not rated | not rated | not rated | not rated |
| 45 | 202.16 | 147.24 | 91.79 | not rated | not rated | not rated |
| 50 | 255.29 | 200.38 | 146.24 | 91.52 | not rated | not rated |
| 55 | 308.13 | 252.90 | 198.82 | 145.43 | 91.36 | not rated |
| 60 | 360.82 | 305.15 | 250.82 | 197.56 | 144.86 | 91.34 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 196.453 | 34.07 | 52.0 |
| Low speed (Y) | 148.378 | 25.74 | 31.4 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 2250 mm |
| F | 2330 mm |
| G | 2850 mm |
| E1 | 1850 mm |
| H | 2500 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.