BE-2x491BB1-B04T C
610.87 kW
Defrost: None
Product code: BE-2X580BC5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 200,690 m³/h |
|---|---|
| External surface | 1,693.4 m² |
| Inner volume | 273.2 dm³ |
| Fin material | Aluminium |
| Net weight | 2,474 kg |
| Quantity | 10 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 18,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2X580BC5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 355.04 | not rated | not rated | not rated | not rated | not rated |
| 40 | 609.07 | 356.12 | not rated | not rated | not rated | not rated |
| 45 | 857.29 | 608.59 | 357.04 | not rated | not rated | not rated |
| 50 | 1103.67 | 855.52 | 608.29 | 357.88 | not rated | not rated |
| 55 | 1349.16 | 1100.59 | 854.05 | 608.10 | 358.81 | not rated |
| 60 | 1594.22 | 1344.88 | 1098.06 | 852.95 | 608.30 | 359.94 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 281.60 | not rated | not rated | not rated | not rated | not rated |
| 40 | 479.54 | 282.40 | not rated | not rated | not rated | not rated |
| 45 | 672.45 | 479.00 | 283.08 | not rated | not rated | not rated |
| 50 | 863.71 | 670.75 | 478.58 | 283.77 | not rated | not rated |
| 55 | 1054.24 | 860.96 | 669.41 | 478.43 | 284.55 | not rated |
| 60 | 1244.32 | 1050.38 | 858.72 | 668.54 | 478.67 | 285.56 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 609.066 | 105.70 | 68.6 |
| Low speed (Y) | 479.537 | 83.22 | 44.9 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 5950 mm |
| F | 2230 mm |
| G | 6550 mm |
| E1 | 1150 mm |
| E2 | 3300 mm |
| H | 6200 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6550 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.