BE-2x691EB5-B04T C
948.48 kW
Defrost: None
Product code: BE-2X780AC5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 284,379 m³/h |
|---|---|
| External surface | 3,409.7 m² |
| Inner volume | 533.9 dm³ |
| Fin material | Aluminium |
| Net weight | 3,883 kg |
| Quantity | 14 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 25,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2X780AC5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 558.64 | not rated | not rated | not rated | not rated | not rated |
| 40 | 948.11 | 559.30 | not rated | not rated | not rated | not rated |
| 45 | 1328.52 | 946.13 | 559.85 | not rated | not rated | not rated |
| 50 | 1705.91 | 1324.06 | 944.43 | 560.48 | not rated | not rated |
| 55 | 2081.91 | 1699.12 | 1320.32 | 943.26 | 561.36 | not rated |
| 60 | 2457.05 | 2072.71 | 1693.39 | 1317.52 | 942.91 | 562.71 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 443.96 | not rated | not rated | not rated | not rated | not rated |
| 40 | 746.38 | 444.32 | not rated | not rated | not rated | not rated |
| 45 | 1040.94 | 744.55 | 444.65 | not rated | not rated | not rated |
| 50 | 1333.03 | 1037.12 | 742.92 | 445.14 | not rated | not rated |
| 55 | 1623.90 | 1327.27 | 1033.92 | 741.93 | 445.84 | not rated |
| 60 | 1914.11 | 1616.27 | 1322.46 | 1031.61 | 741.67 | 446.99 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 948.110 | 164.53 | 83.8 |
| Low speed (Y) | 746.384 | 129.53 | 54.8 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 8850 mm |
| F | 2230 mm |
| G | 9450 mm |
| E1 | 1250 mm |
| E2 | 1200 mm |
| E3 | 3600 mm |
| H | 9100 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 9450 mm |
|---|---|
| Width | 2300 mm |
| Height | 2460 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.