Dry cooler BE-2x491CC1-B04T C

Dry cooler BE-2x491CC1-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x491CC1-B04T C

Heat rejection i
953.02 kW
Air flow
235,993 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 235,993 m³/h
External surface 5,362.4 m²
Inner volume 687.1 dm³
Fin materialAluminium
Net weight 3,835 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 99.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x491CC1-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
953.017 kW Fluid flow 165.29 m³/h Pressure drop 74.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
747.409 kW Fluid flow 129.61 m³/h Pressure drop 48.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 577.21 not rated not rated not rated not rated not rated
40 953.02 575.57 not rated not rated not rated not rated
45 1318.51 947.73 574.21 not rated not rated not rated
50 1680.54 1309.75 943.06 573.13 not rated not rated
55 2040.97 1668.41 1302.05 939.24 572.49 not rated
60 2400.51 2025.53 1657.78 1295.71 936.55 572.57

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 456.92 not rated not rated not rated not rated not rated
40 747.41 455.46 not rated not rated not rated not rated
45 1029.28 742.76 454.11 not rated not rated not rated
50 1308.31 1021.76 738.69 453.03 not rated not rated
55 1586.03 1298.03 1015.18 735.35 452.38 not rated
60 1863.03 1573.04 1289.05 1009.77 732.96 452.33

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 953.017 165.29 74.3
Low speed (Y) 747.409 129.61 48.2

Dimensions

Dimension drawing of BE-2x491CC1-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 10050 mm
F 2330 mm
G 10650 mm
E1 2450 mm
E2 4800 mm
H 10300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10650 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.