BE-t-2x680GC5-B01T C
952.10 kW
Defrost: None
Product code: BE-2x491CC1-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 235,993 m³/h |
|---|---|
| External surface | 5,362.4 m² |
| Inner volume | 687.1 dm³ |
| Fin material | Aluminium |
| Net weight | 3,835 kg |
| Quantity | 8 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 22,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x491CC1-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 577.21 | not rated | not rated | not rated | not rated | not rated |
| 40 | 953.02 | 575.57 | not rated | not rated | not rated | not rated |
| 45 | 1318.51 | 947.73 | 574.21 | not rated | not rated | not rated |
| 50 | 1680.54 | 1309.75 | 943.06 | 573.13 | not rated | not rated |
| 55 | 2040.97 | 1668.41 | 1302.05 | 939.24 | 572.49 | not rated |
| 60 | 2400.51 | 2025.53 | 1657.78 | 1295.71 | 936.55 | 572.57 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 456.92 | not rated | not rated | not rated | not rated | not rated |
| 40 | 747.41 | 455.46 | not rated | not rated | not rated | not rated |
| 45 | 1029.28 | 742.76 | 454.11 | not rated | not rated | not rated |
| 50 | 1308.31 | 1021.76 | 738.69 | 453.03 | not rated | not rated |
| 55 | 1586.03 | 1298.03 | 1015.18 | 735.35 | 452.38 | not rated |
| 60 | 1863.03 | 1573.04 | 1289.05 | 1009.77 | 732.96 | 452.33 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 953.017 | 165.29 | 74.3 |
| Low speed (Y) | 747.409 | 129.61 | 48.2 |
| A | 2880 mm |
|---|---|
| B | 2400 mm |
| C | 10050 mm |
| F | 2330 mm |
| G | 10650 mm |
| E1 | 2450 mm |
| E2 | 4800 mm |
| H | 10300 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 10650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2880 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.