Skip to Content

Dry cooler BE-2x680EC1-B01T C

Dry cooler BE-2x680EC1-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x680EC1-B01T C

Heat rejection i
955.34 kW
Air flow
241,271 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 241,271 m³/h
External surface 3,816.9 m²
Inner volume 782.8 dm³
Fin materialAluminium
Net weight 4,029 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 91.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x680EC1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
955.343 kW Fluid flow 165.70 m³/h Pressure drop 127.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
729.364 kW Fluid flow 126.48 m³/h Pressure drop 79.2 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 579.23 not rated not rated not rated not rated not rated
40 955.34 578.25 not rated not rated not rated not rated
45 1321.88 951.40 577.26 not rated not rated not rated
50 1685.19 1315.17 947.97 576.68 not rated not rated
55 2047.01 1675.80 1309.35 945.29 576.59 not rated
60 2408.01 2034.99 1667.67 1304.74 943.72 577.19

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 446.72 not rated not rated not rated not rated not rated
40 729.36 445.74 not rated not rated not rated not rated
45 1004.25 725.99 444.96 not rated not rated not rated
50 1276.56 998.68 723.18 444.48 not rated not rated
55 1547.70 1268.88 994.02 721.14 444.44 not rated
60 1818.18 1537.93 1262.44 990.52 720.04 445.03

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 955.343 165.70 127.8
Low speed (Y) 729.364 126.48 79.2

Dimensions

Dimension drawing of BE-2x680EC1-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 7650 mm
F 2330 mm
G 8250 mm
E1 1250 mm
E2 1200 mm
E3 2400 mm
H 7900 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 8250 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.