BE-2x491CC1-B04T C
953.02 kW
Defrost: None
Product code: BE-t-2x680GC5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 243,151 m³/h |
|---|---|
| External surface | 2,407.6 m² |
| Inner volume | 416.5 dm³ |
| Fin material | Aluminium |
| Net weight | 3,467 kg |
| Quantity | 12 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 21,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-t-2x680GC5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 572.87 | not rated | not rated | not rated | not rated | not rated |
| 40 | 952.10 | 572.40 | not rated | not rated | not rated | not rated |
| 45 | 1321.17 | 948.39 | 571.96 | not rated | not rated | not rated |
| 50 | 1686.77 | 1314.46 | 945.19 | 571.65 | not rated | not rated |
| 55 | 2050.77 | 1677.20 | 1308.74 | 942.79 | 571.91 | not rated |
| 60 | 2413.88 | 2038.41 | 1669.05 | 1304.32 | 941.44 | 572.80 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 444.67 | not rated | not rated | not rated | not rated | not rated |
| 40 | 731.28 | 444.17 | not rated | not rated | not rated | not rated |
| 45 | 1009.37 | 728.14 | 443.73 | not rated | not rated | not rated |
| 50 | 1284.64 | 1003.91 | 725.52 | 443.57 | not rated | not rated |
| 55 | 1558.62 | 1276.97 | 999.33 | 723.62 | 443.78 | not rated |
| 60 | 1831.88 | 1548.78 | 1270.52 | 995.87 | 722.63 | 444.56 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 952.096 | 165.10 | 105.8 |
| Low speed (Y) | 731.280 | 126.82 | 66.3 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 7050 mm |
| F | 2330 mm |
| G | 7650 mm |
| E1 | 1150 mm |
| E2 | 1100 mm |
| E3 | 2200 mm |
| H | 7300 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 7650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.