BE-2x791EC1-B04T C
1352.48 kW
Defrost: None
Product code: BE-2X980AC1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 371,930 m³/h |
|---|---|
| External surface | 6,032.7 m² |
| Inner volume | 816.2 dm³ |
| Fin material | Aluminium |
| Net weight | 5,606 kg |
| Quantity | 18 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 32,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | D |
| Inlet | 6" |
|---|---|
| Outlet | 6" |
| BE-2X980AC1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 788.20 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1353.94 | 790.96 | not rated | not rated | not rated | not rated |
| 45 | 1902.27 | 1351.32 | 793.31 | not rated | not rated | not rated |
| 50 | 2445.01 | 1895.10 | 1348.96 | 795.45 | not rated | not rated |
| 55 | 2985.08 | 2433.54 | 1888.95 | 1347.47 | 797.86 | not rated |
| 60 | 3523.65 | 2969.45 | 2423.78 | 1884.36 | 1347.08 | 800.69 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 620.15 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1054.28 | 622.20 | not rated | not rated | not rated | not rated |
| 45 | 1473.42 | 1051.80 | 623.90 | not rated | not rated | not rated |
| 50 | 1887.58 | 1467.24 | 1049.71 | 625.54 | not rated | not rated |
| 55 | 2299.42 | 1877.97 | 1462.03 | 1048.33 | 627.41 | not rated |
| 60 | 2709.97 | 2286.49 | 1869.84 | 1458.17 | 1048.00 | 629.79 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1353.935 | 234.97 | 26.2 |
| Low speed (Y) | 1054.276 | 182.86 | 16.7 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 11250 mm |
| F | 2330 mm |
| G | 11850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| E3 | 3600 mm |
| H | 11500 mm |
| D IN | 6" |
| D OUT | 6" |
| Length | 11850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.