BE-2x980AD5-B01T C
1373.48 kW
Defrost: None
Product code: BE-2x891EB1-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 431,939 m³/h |
|---|---|
| External surface | 3,816.9 m² |
| Inner volume | 782.8 dm³ |
| Fin material | Aluminium |
| Net weight | 4,847 kg |
| Quantity | 16 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 44,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 70.0 dB(A) |
|---|---|
| Sound power | 103.0 dB(A) |
| Energy class | E |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x891EB1-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 798.15 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1367.47 | 799.85 | not rated | not rated | not rated | not rated |
| 45 | 1924.09 | 1365.58 | 801.26 | not rated | not rated | not rated |
| 50 | 2476.57 | 1918.87 | 1363.88 | 802.69 | not rated | not rated |
| 55 | 3027.03 | 2468.11 | 1914.27 | 1362.81 | 804.45 | not rated |
| 60 | 3576.47 | 3015.42 | 2460.70 | 1910.93 | 1362.78 | 806.65 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 640.16 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1087.19 | 641.42 | not rated | not rated | not rated | not rated |
| 45 | 1523.23 | 1085.48 | 642.57 | not rated | not rated | not rated |
| 50 | 1955.53 | 1518.85 | 1084.20 | 643.87 | not rated | not rated |
| 55 | 2386.23 | 1948.57 | 1515.19 | 1083.56 | 645.42 | not rated |
| 60 | 2815.95 | 2376.72 | 1942.83 | 1512.80 | 1083.83 | 647.48 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1367.474 | 237.35 | 85.2 |
| Low speed (Y) | 1087.191 | 188.68 | 56.6 |
| A | 2880 mm |
|---|---|
| B | 2400 mm |
| C | 10050 mm |
| F | 2330 mm |
| G | 10650 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| H | 10300 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 10650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2880 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.