BE-2x891EB1-B04T C
1367.47 kW
Defrost: None
Product code: BE-2x980AD5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 367,062 m³/h |
|---|---|
| External surface | 6,375.4 m² |
| Inner volume | 969.4 dm³ |
| Fin material | Aluminium |
| Net weight | 5,860 kg |
| Quantity | 18 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 32,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | D |
| Inlet | 6" |
|---|---|
| Outlet | 6" |
| BE-2x980AD5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 802.71 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1373.48 | 805.57 | not rated | not rated | not rated | not rated |
| 45 | 1925.78 | 1370.61 | 807.91 | not rated | not rated | not rated |
| 50 | 2472.04 | 1918.22 | 1368.12 | 810.12 | not rated | not rated |
| 55 | 3015.40 | 2460.00 | 1911.72 | 1366.51 | 812.54 | not rated |
| 60 | 3557.17 | 2999.09 | 2449.73 | 1906.82 | 1366.07 | 815.53 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 626.64 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1061.58 | 628.85 | not rated | not rated | not rated | not rated |
| 45 | 1480.38 | 1058.95 | 630.68 | not rated | not rated | not rated |
| 50 | 1893.90 | 1473.96 | 1056.75 | 632.38 | not rated | not rated |
| 55 | 2304.98 | 1884.00 | 1468.58 | 1055.36 | 634.34 | not rated |
| 60 | 2714.72 | 2291.74 | 1875.67 | 1464.62 | 1055.04 | 636.84 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1373.482 | 238.23 | 19.9 |
| Low speed (Y) | 1061.579 | 184.11 | 12.4 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 11250 mm |
| F | 2330 mm |
| G | 11850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| E3 | 3600 mm |
| H | 11500 mm |
| D IN | 6" |
| D OUT | 6" |
| Length | 11850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.