BE-2x891EC1-C04C C
1393.00 kW
Defrost: None
Product code: BE-2x980ED1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 332,323 m³/h |
|---|---|
| External surface | 6,151.4 m² |
| Inner volume | 1,154.6 dm³ |
| Fin material | Aluminium |
| Net weight | 5,566 kg |
| Quantity | 18 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 32,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 94.6 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x980ED1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 842.73 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1388.78 | 842.69 | not rated | not rated | not rated | not rated |
| 45 | 1918.49 | 1384.30 | 842.78 | not rated | not rated | not rated |
| 50 | 2442.74 | 1910.10 | 1380.83 | 843.41 | not rated | not rated |
| 55 | 2964.45 | 2430.63 | 1903.38 | 1378.67 | 844.76 | not rated |
| 60 | 3484.76 | 2948.72 | 2420.85 | 1898.82 | 1378.31 | 847.23 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 641.52 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1045.22 | 640.89 | not rated | not rated | not rated | not rated |
| 45 | 1435.93 | 1040.89 | 640.46 | not rated | not rated | not rated |
| 50 | 1822.40 | 1428.39 | 1037.41 | 640.46 | not rated | not rated |
| 55 | 2206.91 | 1811.83 | 1422.27 | 1035.09 | 641.18 | not rated |
| 60 | 2590.35 | 2193.40 | 1803.21 | 1417.94 | 1034.26 | 642.81 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1388.782 | 240.84 | 56.8 |
| Low speed (Y) | 1045.218 | 181.29 | 34.1 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 11250 mm |
| F | 2230 mm |
| G | 11850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| E3 | 3600 mm |
| H | 11500 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 11850 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.