BE-2X980AC1-B01T C
1353.94 kW
Defrost: None
Product code: BE-2x980AD1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 347,861 m³/h |
|---|---|
| External surface | 6,481.9 m² |
| Inner volume | 782.0 dm³ |
| Fin material | Aluminium |
| Net weight | 5,382 kg |
| Quantity | 18 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 32,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x980AD1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 798.34 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1357.96 | 801.17 | not rated | not rated | not rated | not rated |
| 45 | 1898.79 | 1355.34 | 803.59 | not rated | not rated | not rated |
| 50 | 2433.30 | 1891.69 | 1353.24 | 805.99 | not rated | not rated |
| 55 | 2964.85 | 2422.02 | 1885.83 | 1352.07 | 808.43 | not rated |
| 60 | 3494.73 | 2949.53 | 2412.65 | 1881.72 | 1352.26 | 811.84 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 616.08 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1035.97 | 618.01 | not rated | not rated | not rated | not rated |
| 45 | 1439.86 | 1033.37 | 619.64 | not rated | not rated | not rated |
| 50 | 1838.41 | 1433.60 | 1031.24 | 621.30 | not rated | not rated |
| 55 | 2234.49 | 1828.83 | 1428.46 | 1029.96 | 623.33 | not rated |
| 60 | 2629.20 | 2221.72 | 1820.92 | 1424.84 | 1029.89 | 625.93 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1357.959 | 235.53 | 29.4 |
| Low speed (Y) | 1035.972 | 179.64 | 17.9 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 11250 mm |
| F | 2230 mm |
| G | 11850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| E3 | 3600 mm |
| H | 11500 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 11850 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.