BE-291AC1-B04 C
194.88 kW
Defrost: None
Product code: BE-2x180CD1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 43,649 m³/h |
|---|---|
| External surface | 1,440.4 m² |
| Inner volume | 166.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,152 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-2x180CD1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 120.73 | not rated | not rated | not rated | not rated | not rated |
| 40 | 194.39 | 120.12 | not rated | not rated | not rated | not rated |
| 45 | 265.93 | 192.94 | 119.57 | not rated | not rated | not rated |
| 50 | 336.78 | 263.71 | 191.67 | 119.12 | not rated | not rated |
| 55 | 407.33 | 333.83 | 261.78 | 190.63 | 118.82 | not rated |
| 60 | 477.71 | 403.65 | 331.25 | 260.19 | 189.86 | 118.70 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 92.65 | not rated | not rated | not rated | not rated | not rated |
| 40 | 147.68 | 92.13 | not rated | not rated | not rated | not rated |
| 45 | 201.08 | 146.49 | 91.66 | not rated | not rated | not rated |
| 50 | 253.96 | 199.30 | 145.46 | 91.25 | not rated | not rated |
| 55 | 306.62 | 251.62 | 197.76 | 144.55 | 90.99 | not rated |
| 60 | 359.16 | 303.72 | 249.58 | 196.39 | 143.94 | 90.88 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 194.386 | 33.72 | 97.2 |
| Low speed (Y) | 147.677 | 25.61 | 59.6 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 2850 mm |
| F | 2230 mm |
| G | 3450 mm |
| E1 | 2450 mm |
| H | 3100 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3450 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.