BE-t-291GB1-B04 C
193.02 kW
Defrost: None
Product code: BE-2x180CD5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 44,399 m³/h |
|---|---|
| External surface | 1,416.8 m² |
| Inner volume | 194.0 dm³ |
| Fin material | Aluminium |
| Net weight | 1,254 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-2x180CD5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 119.14 | not rated | not rated | not rated | not rated | not rated |
| 40 | 192.86 | 118.56 | not rated | not rated | not rated | not rated |
| 45 | 264.52 | 191.47 | 118.05 | not rated | not rated | not rated |
| 50 | 335.49 | 262.37 | 190.25 | 117.63 | not rated | not rated |
| 55 | 406.17 | 332.62 | 260.48 | 189.23 | 117.33 | not rated |
| 60 | 476.67 | 402.57 | 330.10 | 258.92 | 188.48 | 117.21 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 92.09 | not rated | not rated | not rated | not rated | not rated |
| 40 | 147.65 | 91.59 | not rated | not rated | not rated | not rated |
| 45 | 201.58 | 146.49 | 91.14 | not rated | not rated | not rated |
| 50 | 255.00 | 199.83 | 145.47 | 90.77 | not rated | not rated |
| 55 | 308.18 | 252.67 | 198.29 | 144.63 | 90.52 | not rated |
| 60 | 361.24 | 305.28 | 250.63 | 197.02 | 144.01 | 90.41 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 192.859 | 33.44 | 76.2 |
| Low speed (Y) | 147.650 | 25.61 | 47.4 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 2850 mm |
| F | 2330 mm |
| G | 3450 mm |
| E1 | 2450 mm |
| H | 3100 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3450 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.