BE-2x180CD5-B01T C
192.86 kW
Defrost: None
Product code: BE-t-280HC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 43,920 m³/h |
|---|---|
| External surface | 716.8 m² |
| Inner volume | 96.8 dm³ |
| Fin material | Aluminium |
| Net weight | 724 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-t-280HC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 118.61 | not rated | not rated | not rated | not rated | not rated |
| 40 | 192.57 | 118.13 | not rated | not rated | not rated | not rated |
| 45 | 264.26 | 191.22 | 117.69 | not rated | not rated | not rated |
| 50 | 335.23 | 262.15 | 190.04 | 117.33 | not rated | not rated |
| 55 | 405.86 | 332.37 | 260.29 | 189.07 | 117.10 | not rated |
| 60 | 476.30 | 402.27 | 329.86 | 258.76 | 188.36 | 117.04 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 91.43 | not rated | not rated | not rated | not rated | not rated |
| 40 | 146.92 | 91.00 | not rated | not rated | not rated | not rated |
| 45 | 200.63 | 145.80 | 90.62 | not rated | not rated | not rated |
| 50 | 253.77 | 198.90 | 144.82 | 90.31 | not rated | not rated |
| 55 | 306.67 | 251.47 | 197.40 | 144.02 | 90.10 | not rated |
| 60 | 359.42 | 303.80 | 249.46 | 196.16 | 143.44 | 90.03 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 192.566 | 33.40 | 74.9 |
| Low speed (Y) | 146.917 | 25.48 | 46.3 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 4060 mm |
| F | 1050 mm |
| G | 4660 mm |
| E1 | 1830 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 4660 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.