BE-t-280HC5-B01 C
192.57 kW
Defrost: None
Product code: BE-2x191DC1-C04C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 56,048 m³/h |
|---|---|
| External surface | 633.9 m² |
| Inner volume | 80.4 dm³ |
| Fin material | Aluminium |
| Net weight | 879 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-2x191DC1-C04C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 113.11 | not rated | not rated | not rated | not rated | not rated |
| 40 | 192.15 | 113.26 | not rated | not rated | not rated | not rated |
| 45 | 269.18 | 191.67 | 113.38 | not rated | not rated | not rated |
| 50 | 345.52 | 268.15 | 191.27 | 113.51 | not rated | not rated |
| 55 | 421.59 | 343.96 | 267.24 | 190.96 | 113.69 | not rated |
| 60 | 497.49 | 419.51 | 342.62 | 266.56 | 190.83 | 113.95 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 90.32 | not rated | not rated | not rated | not rated | not rated |
| 40 | 152.24 | 90.41 | not rated | not rated | not rated | not rated |
| 45 | 212.42 | 151.78 | 90.49 | not rated | not rated | not rated |
| 50 | 272.04 | 211.51 | 151.40 | 90.58 | not rated | not rated |
| 55 | 331.40 | 270.69 | 210.73 | 151.13 | 90.71 | not rated |
| 60 | 390.61 | 329.61 | 269.53 | 210.14 | 150.99 | 90.92 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 192.147 | 33.35 | 77.5 |
| Low speed (Y) | 152.244 | 26.42 | 51.2 |
| A | 2511 mm |
|---|---|
| B | 2300 mm |
| C | 2250 mm |
| F | 2230 mm |
| G | 2850 mm |
| E1 | 1850 mm |
| H | 2500 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2250 mm |
|---|---|
| Width | 2300 mm |
| Height | 2511 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.