BE-2x191DC5-B04T C
190.97 kW
Defrost: None
Product code: BE-380BB1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 64,175 m³/h |
|---|---|
| External surface | 581.7 m² |
| Inner volume | 71.1 dm³ |
| Fin material | Aluminium |
| Net weight | 771 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-380BB1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 110.85 | not rated | not rated | not rated | not rated | not rated |
| 40 | 191.30 | 111.17 | not rated | not rated | not rated | not rated |
| 45 | 269.89 | 191.05 | 111.44 | not rated | not rated | not rated |
| 50 | 347.88 | 269.13 | 190.82 | 111.68 | not rated | not rated |
| 55 | 425.60 | 346.65 | 268.49 | 190.68 | 111.94 | not rated |
| 60 | 503.17 | 423.90 | 345.58 | 267.98 | 190.64 | 112.25 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 88.86 | not rated | not rated | not rated | not rated | not rated |
| 40 | 152.32 | 89.10 | not rated | not rated | not rated | not rated |
| 45 | 214.13 | 152.05 | 89.29 | not rated | not rated | not rated |
| 50 | 275.42 | 213.44 | 151.82 | 89.48 | not rated | not rated |
| 55 | 336.47 | 274.33 | 212.84 | 151.66 | 89.68 | not rated |
| 60 | 397.38 | 334.98 | 273.37 | 212.38 | 151.61 | 89.93 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 191.296 | 33.20 | 63.6 |
| Low speed (Y) | 152.315 | 26.44 | 42.4 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 3760 mm |
| F | 1050 mm |
| G | 4360 mm |
| E1 | 1130 mm |
| E2 | 1100 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 4360 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.