Skip to Content

Dry cooler BE-t-291GB1-B04 C

Dry cooler BE-t-291GB1-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-291GB1-B04 C

Heat rejection i
193.02 kW
Air flow
55,407 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 55,407 m³/h
External surface 422.7 m²
Inner volume 55.0 dm³
Fin materialAluminium
Net weight 566 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-t-291GB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
193.024 kW Fluid flow 33.50 m³/h Pressure drop 86.6 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
153.295 kW Fluid flow 26.59 m³/h Pressure drop 57.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 113.04 not rated not rated not rated not rated not rated
40 193.02 113.25 not rated not rated not rated not rated
45 270.93 192.59 113.42 not rated not rated not rated
50 348.13 269.88 192.20 113.61 not rated not rated
55 425.02 346.53 268.99 191.92 113.83 not rated
60 501.74 422.88 345.16 268.30 191.78 114.12

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 90.65 not rated not rated not rated not rated not rated
40 153.30 90.78 not rated not rated not rated not rated
45 214.14 152.88 90.90 not rated not rated not rated
50 274.39 213.24 152.52 91.03 not rated not rated
55 334.35 273.02 212.47 152.27 91.20 not rated
60 394.16 332.53 271.85 211.88 152.16 91.45

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 193.024 33.50 86.6
Low speed (Y) 153.295 26.59 57.4

Dimensions

Dimension drawing of BE-t-291GB1-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1210 mm
C 2860 mm
F 1050 mm
G 3460 mm
E1 1230 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 3460 mm
Width 1210 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.