BE-2x180CD5-B01T C
192.86 kW
Defrost: None
Product code: BE-t-291GB1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 55,407 m³/h |
|---|---|
| External surface | 422.7 m² |
| Inner volume | 55.0 dm³ |
| Fin material | Aluminium |
| Net weight | 566 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-t-291GB1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 113.04 | not rated | not rated | not rated | not rated | not rated |
| 40 | 193.02 | 113.25 | not rated | not rated | not rated | not rated |
| 45 | 270.93 | 192.59 | 113.42 | not rated | not rated | not rated |
| 50 | 348.13 | 269.88 | 192.20 | 113.61 | not rated | not rated |
| 55 | 425.02 | 346.53 | 268.99 | 191.92 | 113.83 | not rated |
| 60 | 501.74 | 422.88 | 345.16 | 268.30 | 191.78 | 114.12 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 90.65 | not rated | not rated | not rated | not rated | not rated |
| 40 | 153.30 | 90.78 | not rated | not rated | not rated | not rated |
| 45 | 214.14 | 152.88 | 90.90 | not rated | not rated | not rated |
| 50 | 274.39 | 213.24 | 152.52 | 91.03 | not rated | not rated |
| 55 | 334.35 | 273.02 | 212.47 | 152.27 | 91.20 | not rated |
| 60 | 394.16 | 332.53 | 271.85 | 211.88 | 152.16 | 91.45 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 193.024 | 33.50 | 86.6 |
| Low speed (Y) | 153.295 | 26.59 | 57.4 |
| A | 1958 mm |
|---|---|
| B | 1210 mm |
| C | 2860 mm |
| F | 1050 mm |
| G | 3460 mm |
| E1 | 1230 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3460 mm |
|---|---|
| Width | 1210 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.