BE-t-2x280GC1-B01T C
330.89 kW
Defrost: None
Product code: BE-2x280AD1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 80,458 m³/h |
|---|---|
| External surface | 1,675.8 m² |
| Inner volume | 211.1 dm³ |
| Fin material | Aluminium |
| Net weight | 1,568 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-2x280AD1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 200.99 | not rated | not rated | not rated | not rated | not rated |
| 40 | 330.87 | 200.67 | not rated | not rated | not rated | not rated |
| 45 | 457.09 | 329.40 | 200.38 | not rated | not rated | not rated |
| 50 | 582.08 | 454.57 | 328.11 | 200.18 | not rated | not rated |
| 55 | 706.52 | 578.57 | 452.38 | 327.11 | 200.17 | not rated |
| 60 | 830.65 | 702.02 | 575.50 | 450.64 | 326.52 | 200.40 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 154.54 | not rated | not rated | not rated | not rated | not rated |
| 40 | 251.53 | 154.21 | not rated | not rated | not rated | not rated |
| 45 | 345.59 | 250.28 | 153.94 | not rated | not rated | not rated |
| 50 | 438.69 | 343.52 | 249.23 | 153.77 | not rated | not rated |
| 55 | 531.35 | 435.83 | 341.78 | 248.46 | 153.77 | not rated |
| 60 | 623.77 | 527.73 | 433.43 | 340.46 | 248.03 | 153.99 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 330.868 | 57.38 | 100.2 |
| Low speed (Y) | 251.532 | 43.63 | 61.6 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 2850 mm |
| F | 2330 mm |
| G | 3450 mm |
| E1 | 1250 mm |
| H | 3100 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3450 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.