BE-2x280CB1-B01C C
330.91 kW
Defrost: None
Product code: BE-480CB5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 90,616 m³/h |
|---|---|
| External surface | 1,910.3 m² |
| Inner volume | 259.1 dm³ |
| Fin material | Aluminium |
| Net weight | 1,636 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.3 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-480CB5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 197.88 | not rated | not rated | not rated | not rated | not rated |
| 40 | 330.92 | 197.54 | not rated | not rated | not rated | not rated |
| 45 | 460.55 | 329.32 | 197.23 | not rated | not rated | not rated |
| 50 | 589.14 | 457.89 | 327.94 | 196.96 | not rated | not rated |
| 55 | 717.21 | 585.38 | 455.52 | 326.79 | 196.82 | not rated |
| 60 | 845.00 | 712.39 | 582.06 | 453.54 | 325.94 | 196.86 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 157.38 | not rated | not rated | not rated | not rated | not rated |
| 40 | 261.00 | 157.01 | not rated | not rated | not rated | not rated |
| 45 | 361.84 | 259.60 | 156.67 | not rated | not rated | not rated |
| 50 | 461.74 | 359.48 | 258.34 | 156.35 | not rated | not rated |
| 55 | 561.21 | 458.46 | 357.39 | 257.30 | 156.18 | not rated |
| 60 | 660.45 | 557.04 | 455.57 | 355.65 | 256.53 | 156.18 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 330.919 | 57.44 | 56.1 |
| Low speed (Y) | 261.001 | 45.26 | 36.6 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 10060 mm |
| F | 1050 mm |
| G | 10660 mm |
| E1 | 2430 mm |
| E2 | 2400 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 10660 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.