Skip to Content

Dry cooler BE-480CB5-B01 C

Dry cooler BE-480CB5-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-480CB5-B01 C

Heat rejection i
330.92 kW
Air flow
90,616 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • D
    Number of fans per row: 4 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 90,616 m³/h
External surface 1,910.3 m²
Inner volume 259.1 dm³
Fin materialAluminium
Net weight 1,636 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.3 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-480CB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
330.919 kW Fluid flow 57.44 m³/h Pressure drop 56.1 kPa
Heat rejection · Low speed (Y)
261.001 kW Fluid flow 45.26 m³/h Pressure drop 36.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 197.88 not rated not rated not rated not rated not rated
40 330.92 197.54 not rated not rated not rated not rated
45 460.55 329.32 197.23 not rated not rated not rated
50 589.14 457.89 327.94 196.96 not rated not rated
55 717.21 585.38 455.52 326.79 196.82 not rated
60 845.00 712.39 582.06 453.54 325.94 196.86

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 157.38 not rated not rated not rated not rated not rated
40 261.00 157.01 not rated not rated not rated not rated
45 361.84 259.60 156.67 not rated not rated not rated
50 461.74 359.48 258.34 156.35 not rated not rated
55 561.21 458.46 357.39 257.30 156.18 not rated
60 660.45 557.04 455.57 355.65 256.53 156.18

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 330.919 57.44 56.1
Low speed (Y) 261.001 45.26 36.6

Dimensions

Dimension drawing of BE-480CB5-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 10060 mm
F 1050 mm
G 10660 mm
E1 2430 mm
E2 2400 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 10660 mm
Width 1210 mm
Height 1808 mm

Downloads