Skip to Content

Dry cooler BE-2x280CB1-B01C C

Dry cooler BE-2x280CB1-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x280CB1-B01C C

Heat rejection i
330.91 kW
Air flow
89,278 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 89,278 m³/h
External surface 1,728.5 m²
Inner volume 211.0 dm³
Fin materialAluminium
Net weight 1,680 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2x280CB1-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
330.908 kW Fluid flow 57.38 m³/h Pressure drop 90.6 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
260.283 kW Fluid flow 45.14 m³/h Pressure drop 59.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 198.14 not rated not rated not rated not rated not rated
40 330.91 197.80 not rated not rated not rated not rated
45 460.40 329.38 197.47 not rated not rated not rated
50 588.76 457.74 328.01 197.21 not rated not rated
55 716.61 585.02 455.39 326.87 197.08 not rated
60 844.18 711.81 581.73 453.46 326.08 197.15

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 157.24 not rated not rated not rated not rated not rated
40 260.28 156.88 not rated not rated not rated not rated
45 360.54 258.88 156.49 not rated not rated not rated
50 459.87 358.20 257.65 156.21 not rated not rated
55 558.77 456.63 356.15 256.63 156.05 not rated
60 657.43 554.64 453.78 354.45 255.90 156.06

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 330.908 57.38 90.6
Low speed (Y) 260.283 45.14 59.1

Dimensions

Dimension drawing of BE-2x280CB1-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 5250 mm
F 2230 mm
G 5850 mm
E1 2450 mm
H 5500 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 5850 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.