BE-t-2x280GC1-B01C C
306.76 kW
Defrost: None
Product code: BE-2x280CB5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 89,592 m³/h |
|---|---|
| External surface | 1,461.3 m² |
| Inner volume | 211.0 dm³ |
| Fin material | Aluminium |
| Net weight | 1,636 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.1 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-2x280CB5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 182.38 | not rated | not rated | not rated | not rated | not rated |
| 40 | 307.02 | 182.20 | not rated | not rated | not rated | not rated |
| 45 | 428.74 | 305.82 | 182.02 | not rated | not rated | not rated |
| 50 | 549.49 | 426.59 | 304.77 | 181.89 | not rated | not rated |
| 55 | 669.78 | 546.41 | 424.71 | 303.89 | 181.85 | not rated |
| 60 | 789.85 | 665.82 | 543.71 | 423.11 | 303.28 | 181.95 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 146.10 | not rated | not rated | not rated | not rated | not rated |
| 40 | 243.96 | 145.86 | not rated | not rated | not rated | not rated |
| 45 | 339.31 | 242.82 | 145.65 | not rated | not rated | not rated |
| 50 | 433.86 | 337.38 | 241.83 | 145.47 | not rated | not rated |
| 55 | 528.03 | 431.15 | 335.68 | 241.02 | 145.39 | not rated |
| 60 | 622.00 | 524.55 | 428.76 | 334.29 | 240.44 | 145.45 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 307.019 | 53.28 | 79.4 |
| Low speed (Y) | 243.962 | 42.34 | 52.8 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 5250 mm |
| F | 2230 mm |
| G | 5850 mm |
| E1 | 2450 mm |
| H | 5500 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 5850 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.