BE-t-480GB1-B01 C
307.42 kW
Defrost: None
Product code: BE-380CD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 66,818 m³/h |
|---|---|
| External surface | 2,824.0 m² |
| Inner volume | 317.5 dm³ |
| Fin material | Aluminium |
| Net weight | 1,586 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-380CD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 193.15 | not rated | not rated | not rated | not rated | not rated |
| 40 | 307.33 | 191.89 | not rated | not rated | not rated | not rated |
| 45 | 418.32 | 304.68 | 190.76 | not rated | not rated | not rated |
| 50 | 528.31 | 414.41 | 302.36 | 189.83 | not rated | not rated |
| 55 | 637.84 | 523.17 | 410.98 | 300.43 | 189.16 | not rated |
| 60 | 747.14 | 631.50 | 518.67 | 408.13 | 298.98 | 188.80 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 147.56 | not rated | not rated | not rated | not rated | not rated |
| 40 | 232.58 | 146.51 | not rated | not rated | not rated | not rated |
| 45 | 315.23 | 230.45 | 145.57 | not rated | not rated | not rated |
| 50 | 397.16 | 312.13 | 228.58 | 144.80 | not rated | not rated |
| 55 | 478.77 | 393.12 | 309.42 | 227.04 | 144.23 | not rated |
| 60 | 560.22 | 473.81 | 389.59 | 307.17 | 225.88 | 143.94 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 307.327 | 53.31 | 94.9 |
| Low speed (Y) | 232.579 | 40.34 | 57.9 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 7660 mm |
| F | 1050 mm |
| G | 8260 mm |
| E1 | 2430 mm |
| E2 | 2400 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 8260 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.